Máxima potencia capacitiva a conectar en bornes de motores trifásicos para la corrección del factor de potencia.

POTENCIA

2 polos

3000 rpm

4 polos

1500 rpm

6 polos

1000 rpm

8 polos

750 rpm

10 polos

600 rpm

12 polos

500 rpm

HP

(1)

(2)

(1)

(2)

(1)

(2)

(1)

(2)

(1)

(2)

(1)

(2)

10

15

20

25

30

40

50

60

75

100

125

150

200

2.5

2.5

5.0

5.0

7.5

10.0

12.5

15.0

17.5

22.5

25.0

32.5

42.0

9

9

9

9

9

9

9

9

9

9

9

9

9

4.0

5.0

5.0

7.5

10.0

10.0

12.5

15.0

17.5

22.5

27.5

35.0

42.5

11

11

10

10

9

9

9

8

8

8

8

8

8

4.0

5.0

5.0

7.5

10.0

10.0

12.5

15.0

17.5

22.5

27.5

35.0

42.5

12

11

11

10

10

10

9

9

8

8

8

8

8

5.0

7.5

7.5

10.5

10.5

12.5

15.0

17.5

20.0

25.0

30.0

37.5

45.0

17

16

15

14

13

12

12

11

11

10

9

9

9

5.0

7.5

10.0

10.0

12.5

15

20.0

22.5

27.5

35.0

40.0

47.5

60.0

23

21

20

19

18

16

15.0

14

13

12

11

11

10

7.5

10.0

12.5

15.0

15.0

17.5

22.5

25.0

30.0

37.5

47.5

55.0

67.5

28

26

24

22

21

19

17

16

15

14

13

13

12

 

(1) Potencia máxima admisible del capacitor en kVAr.

(2) Reducción aproximada de la intensidad de corriente nominal en %.

 

Volver a Factor de Potencia

Volver a Tablas y Fórmulas

 

CONTACTO